Alphamax Specifications

Protocols: TRIP, TAP, ASCII

Discrete Point Inputs: 8

Control Outputs: 2 Form C relay contacts

Maximum Voltage: 60 VDC/120 VAC

Maximum Current: 1 Amp, AC/DC

Interfaces:1 DB25, 1 RJ12

Modem: 212 AT Type 300/1200 baud DTMF/Pulse dial internal modem with DTMF receiver Optional 2400 baud modem.

Dimensions: 5.3" H x 3.1" W x 1.25" D (13.5 cm x 7.9 cm x3.2 cm)

Mounting: wall, frame or rack.

Power Input: +9 to +27 VDC, 133 mA@ 9VDC (1.2 Watts), -48 VDC
Use the AC adapter provided with the AlphaMax or power by DC input. Battery backup available on an
external UPS connector block.

Heat Dissipation: 4.1 BTU, maximum

Operating Temperature: 32°-140° F (0°-60° C)

Operating Humidity: 0%-95% non-condensing

The AlphaMax is the easiest way to install alarm monitoring anywhere you need it: cell towers, railroad crossings, or anywhere else. A complete alarm system in one unit, the AlphaMax sends alarms directly to your numeric or alpha pager. DTMF control lets you acknowledge alarms and operate control with just a phone call. The AlphaMax can also report to ASCII terminals or the T/Mon NOC Remote Alarm Monitoring System.

  • With 8 discrete alarms and 2 control relays, the AlphaMax is the perfect alarm unit for any small-site application.
  • Sends alarm pages directly - no master or extra equipment needed
  • Compact and cost-effective
  • Easiest way to install alarm monitoring wherever you need it
  • 8 discrete alarms, 2 control relays (controlable with derived equations)
  • Reports to numeric and alpha pagers, ASCII terminals, and T/Mon NOC
  • DTMF control - operate relays and ack alarms with just a phone call
  • Correct alarms automatically with derived controls
  • Easy install with your choice of screw-lug or wire-wrap connector blocks
  • Easy configuration with included Windows software
  • AC or DC power
  • 3 hours of backup power with optional UPS
  • Dial-up access to a PBX, switch, server, or radio through optional reach-through port
Next Page: Summary of AlphaMax Benefits
PDFDownload White Paper

Get a Custom Application Diagram of Your Perfect-Fit Monitoring System

There is no other network on the planet that is exactly like yours. For that reason, you need to build a monitoring system that's the right fit for you.

"Buying more than you need" and "buying less than you need" are real risks. You also have to think about training, tech support, and upgrade availability.

Send me a quick online message about what you're trying to accomplish. I'll work with you to build a custom PDF application diagram that's a perfect fit for your network.


Make an Informed Decision


Your network isn't off-the-shelf.

Your monitoring system shouldn't be, either.

Customized monitoring application drawing

We'll walk you through this with a customized monitoring diagram.

Just tell us what you're trying to accomplish with remote monitoring.

Get a Custom Diagram