Overview: TempDefender IT

star Average user rating: 4.5 out of 5 stars based on 11 reviews from the install base.
TempDefender IT (front panel)
"Your server room guardian..."
Designed to protect your equipment rooms from unseen threats...
  • Small form-factor saves on valuable rack space
  • Plug 'n' Play design - Start monitoring in minutes
  • SNMP-compatible - Send traps to your SNMP manager
3D TempDefender
  • Receive 24/7 email notifications when environmentals cross your thresholds
  • 4 D-Wire sensor inputs (each D-Wire sensor port supports multiple "daisy-chained" sensors, with a max. of 16 sensors per unit)
  • Telco-grade casing for enhanced durability
  • Built-in web interface to monitor from any PC on the network
  • Monitor temp, environmental, and security conditions in your server room or data center
  • Private VLAN Support
  • Spring clamp connectors for easy alarm termination

Could you estimate how much money your company has invested in your IT server room or data center? How much is your network uptime worth to you? These questions might be difficult to answer, but monitoring your valuable IT equipment certainly doesn't have to be.

Meet the TempDefender IT
The TempDefender keeps tabs on all the environmental levels that affect your servers, phone closets, data centers, and other equipment locations. The 8 discrete alarms on the back panel of the TempDefender monitor your dry contacts, such as motion sensors, UPS, smoke detectors, flood sensors, AC and room entry. The 4 D-wire sensor inputs on the back panel allow you to monitor up to 16 analog sensors, giving you the analog capacity to keep on top of environmental conditions at your site.


Client Reviews



Full Specifications


TempDefender IT (Back Panel)
The TempDefender IT can monitor your server room/closet with smoke detectors, humidity sensors, floor water sensors, temperature sensors, and more.
Full Specifications.
Discrete Alarms. 8
D-Wire Sensor Inputs. 4 (up to 16 sensors via daisy chaining).
Control Relays. 1 or 3 (for Tower Lights) build options.
Ping Targets. 32.
Interfaces. Spring clamp connectors for discretes and relays.
4 - RJ12 jacks for digital sensors.
1 RJ45 10/100BaseT Ethernet port.
1 Barrel plug connector for unit power.
(Other power connectors available upon request).
Network Security. VLAN.
Protocols. SNMPv1 and SNMPv2c.
HTTP or HTTPS.
Telnet.
DCPx.
Email (up to 8 email addresses).
ICMP.
Dimensions. 4"L x 11.5"W x 1.7"H
Weight. 1.5 lbs.
Mounting. 19" rack or wall mount
Power Input. +24VDC via 110VAC wall transformer (12V to 30VDC)
-48VDC (-36 to -58VDC) optional
-24VDC (-18 to -36VDC) optional
+12VDC (+11 to +30VDC) optional
130VDC optional
Audible Notification. Yes, via front panel speaker.
Operating Temperature. 32 to 140 degrees F (0 to 60 degrees C).
Operating Humidity. 0% - 95% non-condensing
RoHS. Yes (5/6).

Temperature Monitor Guide

Data Center Management Techniques


Screenshots and Descriptions

The TempDefender IT includes an easy-to-navigate web interface that boasts several time-saving new tools. Menus load very quickly, and alarm statuses update automatically without requiring a page refresh. Look below for screens of the new setup wizards that make it easy to configure email and SNMP notification schedules.

The TempDefender Sensor Monitoring Interface
Monitor Real-Time Sensor Readings - monitoring your analog values has never been easier. Each sensor displays its monitored values in gauge form - so you can easily see the status of your alarms in a graphical display.

The TempDefender Sensor Setup Interface
Easy-to-Configure Analog Sensors - When you plug in a sensor, the TempDefender will automatically determine the sensor's type and necessary settings. You don't have to worry about reference values or other complicated settings. Just plugin the sensor, set your thresholds, and you're ready to go.

TempDefender Base Alarms

Keep tabs on your dry contact alarms: - Use the 8 discrete alarms to track thinks like tripped motion sensors, crossed temperature thresholds, and building entry.

View the MonitorControls menu up close See the SNMP setup screen
Monitor and Operate Controls: Get an at-a-glance view on the state of the control relays. You can latch and release controls from this screen. Setup SNMP Traps: Select the event that must occur for SNMP traps. You have the option of receiving traps when alarms are triggered, when they clear, or both.
View Configurable Email Settings See how to create alarm notification schedules
Setup Email Notifications: Whether you check emails at your desk or from your smartphone, the TempDefender keeps you in the loop. Have your SMTP server and port information handy during setup. Creating Alarm Schedules: The built-in alarm scheduling tool allows you to account for employee time-off, after-hours monitoring, and shift changes. Enter in the specific day(s) and times you want to receive alarm notifications.

TempDefender Sensor Ordering Options

D-Wire Sensor
Track your environmentals with D-Wire Sensors

D-Wire sensors are a way to track environmentals in your server room (wide range temperature support: -40 to 180 degrees F), PBX closet, or data center using minimum analog capacity. With the TempDefender's D-Wire sensors, you don't have to worry about analog capacity on your RTUs, tangled masses of sensors at your RTU, or even the trouble of wiring analog connectors.

D-Wire sensors from DPS use simple RJ-11 connectors, in and out, and allow you to chain up to 16 sensors to a single TempDefender D-Wire port. Your sensor chain can run a maximum of 600 feet, so you can run sensors out as far as you need to monitor your equipment, without having to place analog-capable RTUs in multiple places. Note: Internal D-Wire sensors (for internal temperature or internal voltage monitoring, for example) impact total sensor cable length.

The maximum length of a D-Wire daisy chain varies depending on the number of sensor nodes in the chain. A single sensor can receive power and transmit data over 600 feet of wire (for example, 3 sensors could have lengths less than or equal to 200 feet). Adding sensors to the chain consumes more power and reduces the maximum allowable wire length, as described in the table below:

D-Wire Temp

Temperature Sensor. (D-PK-DSNSR-12001)

Temperature sensor that connects to the DPS Sensor network. This sensor can report live-analog values for monitoring temperature within +/-2 degrees F.


D-Wire Temp/Humidity

Temperature & Humidity Sensor. (D-PK-DSNSR-12002.00002)

Monitor temperature and humidity using the D-Wire Temperature and Humidity combination sensor. This device can accurately report the live-anlog values for temperature (+/- 2 degrees F) and humidity (+/0 4% RH).


D-Wire Temp w/ LED

Temperature Sensor w/ LED. (D-PK-DSNSR-12003)

An additional LED on this D-Wire Temperature Sensor gives a visual notification on the sensor. Much like the standard Temperature Sensor, this device will monitor live-analog values and can report temperature within +/- 2 degrees F of the actual value.


D-Wire Batt.Cell

Batt.Cell Voltage Sensor. (D-PK-DSNSR-12004)

Battery Voltage Monitor & Temperature Probe that connects into the DPS Sensor network. This sensor is ideal for the digital inputs located on the Battery Voltage Monitor G2. Battery voltage range options include: 0VDC - 5VDC, 0VDC - 12VDC, 0VDC - 16VDC, and 0VDC - 60VDC.


D-Wire External Sensor Probe

Temperature External Sensor Probe. (D-PK-DSNSR-12008)

External 8 foot temperature probe that is compatible with the DPS sensor network. This sensor may be plugged directly into a D-Wire point of a DPS RTU or may be the terminating point of a daisy chain of D-wire sensors. Note: This sensor probe is not daisy chainable.



Maximum Allowable D-Wire Cable Length
Sensor Nodes Max Length (ft)
1600
2600
3600
4600
5600
6600
7600
8600
9600
10600
11600
12600
13600
14600
15600
16600
Note: Distances will vary depending on D-Wire capable RTU. Consult applicable product section for product-specific D-Wire information. DPS recommends that no more than 16 sensors are used on a single chain, although up to 32 are supported on some platforms.
D-Wire Temperature and Humidity Sensor Full Specifications
Dimensions: 2.25"H x 1.625"W x .9375"D
Weight: 0.38 lb
Operating Temperature: -40 to 180 degrees F (-40 to 82.2 degrees C)
Accuracy +/- 2 degrees F and +/- 4% RH
Aggregate Length: 40 to 800 feet

Data Center Management Techniques


TempDefender Applications

The Temp Defender reports via T/Mon, SNMP, the TempDefender Web Browser, and E-Mail notifications.
The TempDefender is capable of reporting discrete and analog threshold alarms a number of ways, keeping you in the loop.
  • Report to your T/Mon master, so your NOC personnel always know what's going on at the TempDefender's site
  • Send SNMP Traps
  • The Temp Defender's Web interface allows technicians to connect directly to the temp defender for simple configuration and monitoring.
  • The Temp Defender can also send email notifications, so you can keep track of alarms from your smartphone, laptop, or any workstaiton where you can access email. You can even acknowledge the emails by clickable link within the email notification.

D-Wire Sensors make running analog sensors painless.

D-Wire sensors are all powered directly from the Temp Defender D-Wire ports and support 4 analog thresholds (major under, minor under, minor over, major over). You can daisy chain these sensors together, up to 16 to a single TempDefender, in any configuration. Run 16 sensors (at a maximum of 600 feet) in a single chain or run four sensors from each of the TempDefender's D-Wire ports.

D-Wire Temperature Sensor

D-Wire Temperature Sensor




To receive a price quote or ROI analysis...

Call 1-800-693-0351.

Need a Quote?

Get it by: 4:15 PM Friday (tomorrow)

Now: 4:47 PM
Next Step:
Send Us Your Quote Request
8:00 AM Friday
We'll Start Work on Your Detailed Quote
4:15 PM Friday
Get Your Quote (Email PDF)

It's 4:47 PM on Thursday at our Fresno, CA, USA headquarters. It's late in the day, but we promise to start on your quote first thing in the morning.

Get a Quote