APD Full Specifications

Back panel option #1: screw-down connectors:
Alarm Point Duplicator Back Panel
Back panel option #2: 50-pin amphenol connectors:
Alarm Point Duplicator Back Panel

The Alarm Point Duplicator is available with either screw-down connectors (shown on top) or 50-pin amphenol connectors (shown on bottom) for the discrete inputs and control relay outputs.
Full Specifications
Protocols:

SNMPv1 and v2c, DCP, DCPf, DCPx, DCP1,HTTP, Telnet, ICMP

Discrete Inputs:

32 (opto-isolated)

Output Relays:

64

Maximum Voltage: 60 VDC/120 VAC
Maximum Current: 3 Amp AC/DC
Analog Inputs: 2 Power Feed analog channels
Analog Accuracy: +/- 1% of actual value
Power Input: Dual Feed -48VDC (-36 to -72 VDC)
(Optional) -24 VDC (-18 to -36 VDC)
(Optional) Wide Range -24/-48 VDC (-18 to -72 VDC)
(Optional) +24VDC (+18 to +36 VDC)
(Optional) 110 VAC wall transformer
(Optional) 220 VAC (UK) wall transformer
Interfaces:

1 RJ45 10/100 Ethernet port
1 DB9 Craft Port
24 8-pin screw plug for analogs, or...
(Optional) 6 50-pin Amphenol connectors for alarm inputs & relay outputs

Visual Interface: 35 front-panel LEDs
5 back-panel LEDs
Dimensions:

3.47" (1 RU) H x 17"W x 7.336"D

Mounting: 19" or 23" rack
Fuse: 0.75 amp GMT
Operating Temperature: 32 - 140 F (0 - 60 C)
Operating Humidity: 0%-95% noncondensing
RoHS: 5 of 6

Need a Quote?

Get it by: 4:15 PM Friday (today)

Now: 6:03 AM
Next Step:
Send Us Your Quote Request
8:00 AM Friday
We'll Start Work on Your Detailed Quote
4:15 PM Friday
Get Your Quote (Email PDF)

It's 6:03 AM on Friday at our Fresno, CA, USA headquarters. It's early in the morning, but we'll start on your quote as soon as we get into the office.

Get a Quote
Sitemap