Critical Alarm Enunciator: Full Specifications

Critical Alarm Enunciator
The Critical Alarm Enunciator receives input from your monitored devices, provides local notification, and relays alarms to your existing alarm collection equipment.
Full Specifications
Analog Alarm Inputs: 1 (battery monitor input)
Voltage Monitoring Range: +21.5 to +30.0 VDC
Voltage Alarm Thresholds For VRLA:
High Voltage: +28.5 VDC
Low Voltage (LV1): +26.0 VDC
Very Low Voltage (LV2): +23.0 VDC
Voltage Alarm Thresholds For flooded system:
High Voltage: +27.9 VDC
Low Voltage (LV1): +25.4 VDC
Very Low Voltage (LV2): +22.4 VDC
Discrete Point Inputs: 3 (reversible)
Control Outputs: 6 (alarm relay outputs)
Maximum Voltage: 60 VDC/120 VAC
Maximum Current: 1/2 Amp AC/DC
Visual Display: 6 unicolor LEDs
3 digit display
Speaker Volume: 0-85 dB at 30 cm
Dimensions: 5"H x 4"W x2"D (12.7cm x 10.2cm x 5.1cm)
Weight: 3 lbs. (1.4kg)
Mounting: Wall mount
Power Input: +24 VDC
Current Draw: 550 mA
Fuse: 1 Amp GMT
Operating Temperature: 32° to 140° F (0° - 60° C)
Operating Humidity: 0%-95% noncondensing