| Full Specifications | |
|---|---|
| AC Inputs: | 1 AC input feed with 8 outputs OR 2 AC inputs with 3 outputs each AC inputs support 20 amps max current at 120 VAC |
| Outputs: | Max output is 10 amps per outlet |
| Discrete alarms: (RTU Build Only) | 16 |
| Analogs: (RTU Build Only) | 2 |
| Analog Accuracy: (RTU Build Only) | +/- 1% of actual value |
| Controls: (RTU Build Only) | 2 |
| Control Relay Commands: | On, Off and Reset (off-on) |
| Control Buttons: | Located on the front panel; used for switching power on/off while on-site |
| Interfaces: | 1 DB9 craft port 1 - 50-pin Amphenol connector for discretes, analogs, & controls (RTU Build Only) 1 - 10BaseT LAN port 1 RS485 expansion port for daisy-chaining add'l switches 1 stereo jack for external temperature probe |
| Web interface: | Yes; supports HTTPS via SSL encryption |
| Current Draw Monitoring: | Yes, on each AC input |
| Mounting: | Rack mountable; 1 rack unit (RU) |
| Firmware Upgrade: | Upgradeable via LAN or serial |
| TTY Interface: | Yes, for turn-up and AC switch control |
| RoHS 5 Approved | Yes |