The KDA provides 64 reversible alarm inputs (56 ground closure, 8 dual opto), 8 N.O. relay form A contacts, wire wrap connectors, rack mountable 19" & 23".
| Full Specifications | |
|---|---|
| Dimensions: | 17" W x 12" D x 1.75" H |
| Mounting: | 19" or 23" rack mounting |
| Power Input: | -21 to -30 VDC (260 ma/6.25w @ 24 VDC). -43 to -56 VDC (130 ma/6.25w @ 48 VDC). |
| Fuse: | 1/4 Amp. |
| Modem: | 212 "AT" type 1200 Baud |
| Protocols: | SNMP, TBOS, TRIP, DCP, DCPF, DCPS, TL-1 |
| TBOS Inputs: |
8 ports with 8 displays per port |
| Interface: | RS422/485 |
| Data Rate: | 1200/2400 Baud |
| Relay Contacts (control outputs and fuse alarm): |
Initial Contact Resistance: 50 milleohms |
| Weight: | 3 lbs. |
| Voltage Range: | Option 0 = -21 to -56 VDC Option 2 = -21 to -30 VDC Option 4 = -43 to -56 VDC |
| Electrical Life: | 500,000 Operations (1A @ 30VDC) |
| Temperature: | Option 01: 0 to +60 Degrees C. Option 05: -30 to +70 Degrees C. |
| Humidity: | 0% to 95% non-condensing |
Give Us a Call!
To find out more about this and other DPS applications, give us a call at our toll-free number and talk to one of our network specialists. They'll help you put together a perfect fit solution for your network!
Sales: 1-800-693-0351 · Fax: 559-454-1688