| Full Specifications | |
|---|---|
| Analog Alarm Inputs: | 1 (battery monitor input) |
| Voltage Monitoring Range: | +21.5 to +30.0 VDC |
| Voltage Alarm Thresholds For VRLA: | |
| High Voltage: | +28.5 VDC |
| Low Voltage (LV1): | +26.0 VDC |
| Very Low Voltage (LV2): | +23.0 VDC |
| Voltage Alarm Thresholds For flooded system: | |
| High Voltage: | +27.9 VDC |
| Low Voltage (LV1): | +25.4 VDC |
| Very Low Voltage (LV2): | +22.4 VDC |
| Discrete Point Inputs: | 3 (reversible) |
| Control Outputs: | 6 (alarm relay outputs) |
| Maximum Voltage: | 60 VDC/120 VAC |
| Maximum Current: | 1/2 Amp AC/DC |
| Visual Display: | 6 unicolor LEDs 3 digit display |
| Speaker Volume: | 0-85 dB at 30 cm |
| Dimensions: | 5"H x 4"W x2"D (12.7cm x 10.2cm x 5.1cm) |
| Weight: | 3 lbs. (1.4kg) |
| Mounting: | Wall mount |
| Power Input: | +24 VDC |
| Current Draw: | 550 mA |
| Fuse: | 1 Amp GMT |
| Operating Temperature: | 32° to 140° F (0° - 60° C) |
| Operating Humidity: | 0%–95% noncondensing |